LC1G150BEEA
Schneider Electric
Contactor, high power, TeSys Giga, advanced version, AC-3, <= 440V, 150A, 3 pole/NO, 24-48VAC/DC coil
Disponible
Obtenez un devis maintenant
- "TeSys Giga high power contactor, 3 poles (3 NO) for category AC-3 applications up to 150A 90kW@440V. It provides a 24-48V AC/DC wide band low consumption electronic coil, PLC output control and embedded highly reliability 1NO+1NC auxiliary contact block (17V 1mA). Designed for demanding applications with maximum operating rates up to 600 cycles per hour and environments until 60\u00b0C. It procures high reliability and durability with 5 Mcycles mechanical durability. Local and Remote Contact Wear Diagnosis (CWD) as standard function, continuous monitoring with healthy and alarm indicators. It is possibility to replace switching module (main contacts), enhancement contactor life. Contactor can be fixed in all quadrants, maintenance without removing cables/busbars, and OLR could be directly mounted below contactor. To be used with power connection by bolted connection with cable memory kit and control connections by spring terminals, accessible from front for easy and quick replacement. It provides IP2x protection in Front face with shrouds conforming to IEC 60529 and VDE 0106. It can cover -25\u00b0C to 60\u00b0C operation ambient air temperature and directly mounted on plate, No derating up to 3000m altitude. The dimension is 255mm x 108mm x 175mm (H x W x D), compact size enables panel space savings. Multi standards certified(CE,CB,CCC,cULus,EAC,KC,RCM,Marine) and Green Premium compliant (RoHs/Reach). Unique QR code provides quick access to complete product data."
| Specification | Value |
|---|---|
| Product Certifications | CB Scheme || CCC || cULus || EAC || CE || UKCA || EU-RO-MR by DNV-GL |
| Height | 255 mm |
| Power Dissipation Per Pole | 10 W AC-1 - Ith 275 A || 5 W AC-3 - Ith 150 A |
| Average Impedance | 0.00018 Ohm |
| Auxiliary Contact Composition | 1 NO + 1 NC |
| Connection Pitch | 35 mm |
| [Ith] Conventional Free Air Thermal Current | 275 A (at 40 °C) |
| Standards | EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || JIS C8201-4-1 || JIS C8201-5-1 |
| Mounting Support | plate |
| Hold-In Power Consumption In W | 5.7-5.7 W |
| Rated Breaking Capacity | 1280 A at 440 V |
| Irms Rated Making Capacity | 1890 A at 440 V |
| Associated Fuse Rating | 160 A aM at <= 440 V for motor || 160 A aM at <= 690 V for motor || 315 A gG at <= 690 V |
| Net Weight | 4.1 kg |
| [Uimp] Rated Impulse Withstand Voltage | 8 kV |
| Inrush Power In Va | 290-290 VA |
| Pole Contact Composition | 3 NO |
| Connections - Terminals | power circuit: bar 2 - busbar cross section: 25 x 6 mm || power circuit: lugs-ring terminals 1 185-185 mm² || power circuit: bolted connection || control circuit: push-in 1 0.2-2.5 mm² - cable stiffness: solid stranded without cable end || control circuit: push-in 1 0.25-2.5 mm² - cable stiffness: flexible with cable end || control circuit: push-in 2 0.5-1.0 mm² with cable end || control circuit: push-in 0.75-2.5 mm² - cable stiffness: solid stranded without cable end || control circuit: push-in 0.75-2.5 mm² - cable stiffness: flexible with cable end |
| Coil Technology | built-in bidirectional peak limiting |
| Operating Time | 40...70 ms closing || 15...50 ms opening |
| Maximum Operating Rate | 600 cyc/h AC-3 || 600 cyc/h AC-3e || 300 cyc/h AC-1 || 150 cyc/h AC-4 |
| Mechanical Durability | 8 Mcycles |
| Tightening Torque | 18 N.m |
| Compatibility Code | LC1G |
| Hold-In Power Consumption In Va | 10-10 VA |
| Width | 108 mm |
| Overvoltage Category | III |
| Depth | 193 mm |
| Maximum Horse Power Rating | 40 hp at 200/208 V 60 Hz || 50 hp at 230/240 V 60 Hz || 100 hp at 460/480 V 60 Hz || 125 hp at 575/600 V 60 Hz |
| Motor Power Kw | 37 kW at 230 V AC 50/60 Hz (AC-3e) || 75 kW at 400 V AC 50/60 Hz (AC-3e) || 75 kW at 415 V AC 50/60 Hz (AC-3e) || 90 kW at 440 V AC 50/60 Hz (AC-3e) || 90 kW at 500 V AC 50/60 Hz (AC-3e) || 90 kW at 690 V AC 50/60 Hz (AC-3e) || 75 kW at 1000 V AC 50/60 Hz (AC-3e) || 37 kW at 230 V AC 50/60 Hz (AC-3) || 75 kW at 400 V AC 50/60 Hz (AC-3) || 75 kW at 415 V AC 50/60 Hz (AC-3) || 90 kW at 440 V AC 50/60 Hz (AC-3) || 90 kW at 500 V AC 50/60 Hz (AC-3) || 90 kW at 690 V AC 50/60 Hz (AC-3) || 75 kW at 1000 V AC 50/60 Hz (AC-3) || 37 kW at 230 V AC 50/60 Hz (AC-4) || 75 kW at 400 V AC 50/60 Hz (AC-4) || 75 kW at 415 V AC 50/60 Hz (AC-4) || 80 kW at 440 V AC 50/60 Hz (AC-4) || 90 kW at 500 V AC 50/60 Hz (AC-4) || 90 kW at 690 V AC 50/60 Hz (AC-4) || 75 kW at 1000 V AC 50/60 Hz (AC-4) |
| [Ui] Rated Insulation Voltage | 1000 V |
| Inrush Power In W | 220 W |
| [Icw] Rated Short-Time Withstand Current | 1.2 kA - 10 s || 0.7 kA - 30 s || 0.6 kA - 1 min || 0.45 kA - 3 min || 0.35 kA - 10 min |
| [Uc] Control Circuit Voltage | 24...48 V AC 50/60 Hz || 24...48 V DC |
| [Ue] Rated Operational Voltage | <= 1000 V AC 50/60 Hz || <= 460 V DC |
| Range Of Product | TeSys Giga |
| Control Circuit Voltage Limits | operational: 0.8 Uc Min...1.1 Uc Max (at <60 °C) || drop-out: 0.1 Uc Max...0.45 Uc Min (at <60 °C) |
| Contactor Application | power switching || motor control |
| Product Or Component Type | contactor |
| Range | TeSys |
| Utilisation Category | AC-1 || AC-3 || AC-3e || AC-4 || AC-5a || AC-5b || AC-6a || AC-6b || AC-8a || AC-8b || DC-1 || DC-3 || DC-5 |
| [Ie] Rated Operational Current | 275 A (at <40 °C) at <= 1000 V AC-1 || 150 A (at <60 °C) at <= 440 V AC-3 |
| Poles Description | 3P |
| Device Short Name | LC1G |
Nos articles d'occasion et nos options de réparation sont assortis d'une garantie Obso de 12 mois.
"Super service ! Tout a été traité très rapidement et avec compétence et l'assistance personnelle était excellente. Je choisirai toujours Obso Automation ! Merci beaucoup pour votre soutien." - MJ
Des options de livraison standard sont également disponibles si nécessaire.
"Professionnel, courtois et précis. La pièce obsolète a fait l'objet d'un devis le jour même et a été livrée le lendemain" - PT
1
Step 1
Partie ajoutée pour enquête
2
Étape 2
Votre gestionnaire de compte personnel est déjà sur le coup et vous fournit des réponses rapides avec un service imbattable.
3
Étape 3
Nous ne nous contentons pas de traiter les commandes, nous garantissons une livraison sans heurts, une transparence totale et une absence totale de maux de tête.
4
Étape 4
Plus de 10 000 clients nous font confiance pour une bonne raison. Obtenez votre devis dès maintenant et découvrez l’automatisation sans risque, ni délai, ni incertitude.
Google Reviews