LC2D80AKUE

Schneider Electric

TeSys Deca reversing contactor 3P 66A AC-3/AC-3e up to 440V coil 100-250V AC/DC

Disponibile

Richiedi un preventivo adesso

  • "TeSys D reversing contactor, 3 poles (3NO), for motor control applications up to 9A/690V AC-3 (4kW@400V). It provides low consumption 100-250V AC/DC coils with electronic control, 2NO+2NC built-in auxiliary contacts (NC mirror contacts), connection by screw clamp terminals. For operating rates until 3600 cycles/hour and environments until 60\u00b0C, it procures high reliability and durability. Compact (90mm width), DIN-rail mounting or screw fixing. With pre-wired reversing power connections, mechanical interlock (without electrical interlocking). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh)."
Per saperne di più arrow Weniger lesen arrow
Specification Value
Non-Overlap Time 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Minimum Switching Current 5 mA for signalling circuit
Control Circuit Voltage Limits <= 0.1 Uc -40-70 °C drop-out AC/DC || 0.85...1.1 Uc -40-60 °C operational AC/DC || 1...1.1 Uc 60-70 °C operational AC/DC
Hold-In Power Consumption In W 1.2-1.2 W 20 °C
Insulation Resistance > 10 MOhm for signalling circuit
Inrush Power In Va 18-18 VA 50/60 Hz 20 °C)
Coil Technology built-in bidirectional peak limiting
Minimum Switching Voltage 17 V for signalling circuit
Signalling Circuit Frequency 25...400 Hz
Heat Dissipation 1.2-1.2 W 50/60 Hz
Inrush Power In W 14-14 W 20 °C
Auxiliary Contacts Type mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Hold-In Power Consumption In Va 1.8-1.8 VA 20 °C) 50/60 Hz
Interlocking Type mechanical
[Uc] Control Circuit Voltage 100...250 V AC 50/60 Hz || 100...250 V DC
[Ue] Rated Operational Voltage power circuit 690 V AC 25...400 Hz
Power Dissipation Per Pole 9.6 W AC-1 || 6.5 W AC-3 || 6.5 W AC-3e
Average Impedance 1.5 mOhm - Ith 80 A 50 Hz for power circuit
Auxiliary Contact Composition 1 NO + 1 NC
[Ith] Conventional Free Air Thermal Current 10 A (at 60 °C) for signalling circuit || 80 A (at 60 °C) for power circuit
Mounting Support plate || rail
Control Circuit Type AC 50/60 Hz AC/DC electronic || DC AC/DC electronic
Standards EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || IEC 60335-1
Safety Reliability Level B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Contactor Application resistive load || motor control
Rated Breaking Capacity 1000 A at 440 V for power circuit conforming to IEC 60947
Product Or Component Type reversing contactor
Product Certifications CCC || CSA || EAC || UL || KC || DNV-GL || LROS (Lloyds register of shipping) || UKCA
Irms Rated Making Capacity 140 A AC for signalling circuit conforming to IEC 60947-5-1 || 250 A DC for signalling circuit conforming to IEC 60947-5-1 || 1000 A at 440 V for power circuit conforming to IEC 60947
Product Name Tesys Deca green || TeSys Deca
Associated Fuse Rating 10 A gG for signalling circuit conforming to IEC 60947-5-1 || 125 A gG at <= 690 V coordination type 1 for power circuit || 125 A gG at <= 690 V coordination type 2 for power circuit
[Uimp] Rated Impulse Withstand Voltage 6 kV IEC 60947
Connections - Terminals control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || power circuit EverLink BTR screw connectors 1 1-35 mm²flexible with cable end || power circuit EverLink BTR screw connectors 2 1-25 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid || control circuit screw clamp terminals 2 1-4 mm²solid || power circuit EverLink BTR screw connectors 1 1-35 mm²solid || power circuit EverLink BTR screw connectors 2 1-25 mm²solid || control circuit screw clamp terminals 1 1-4 mm²flexible || control circuit screw clamp terminals 2 1-4 mm²flexible || power circuit EverLink BTR screw connectors 1 1-35 mm²flexible || power circuit EverLink BTR screw connectors 2 1-25 mm²flexible
Range TeSys || TeSys Deca
Pole Contact Composition 3 NO
Device Presentation preassembled with reversing power busbar
Utilisation Category AC-1 || AC-3 || AC-3e
[Ie] Rated Operational Current 80 A (at <60 °C) at <= 440 V AC-1 for power circuit || 66 A (at <60 °C) at <= 440 V AC-3 for power circuit || 66 A (at <60 °C) AC-3e for power circuit
Operating Time 55...65 ms closing || 20...80 ms opening
Maximum Operating Rate 3600 cyc/h 60 °C
Electrical Durability 1 Mcycles 66 A AC-3 <= 440 V || 0.5 Mcycles 80 A AC-1 <= 440 V || 1 Mcycles 66 A AC-3e
Tightening Torque control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 8 N.m EverLink BTR screw connectors 25-35 mm² hexagonal 4 mm || power circuit 5 N.m EverLink BTR screw connectors 1-25 mm² hexagonal 4 mm
Poles Description 3P
Overvoltage Category III
Motor Power Kw 18.5 kW at 220...230 V AC 50 Hz || 37 kW at 380...400 V AC 50 Hz || 37 kW at 415 V AC 50 Hz || 37 kW at 440 V AC 50 Hz || 37 kW at 500 V AC 50 Hz || 37 kW at 660...690 V AC 50 Hz
Maximum Horse Power Rating 5 hp at 115 V AC 60 Hz for 1 phase motors || 10 hp at 230/240 V AC 60 Hz for 1 phase motors || 20 hp at 200/208 V AC 60 Hz for 3 phase motors || 20 hp at 230/240 V AC 60 Hz for 3 phase motors || 40 hp at 460/480 V AC 60 Hz for 3 phase motors || 50 hp at 575/600 V AC 60 Hz for 3 phase motors
[Ui] Rated Insulation Voltage power circuit 690 V IEC 60947-4-1 || signalling circuit 690 V IEC 60947-1
Mechanical Durability 6 Mcycles
Device Short Name LC2D
[Icw] Rated Short-Time Withstand Current 100 A - 1 s for signalling circuit || 120 A - 500 ms for signalling circuit || 140 A - 100 ms for signalling circuit || 520 A 40 °C - 10 s for power circuit || 900 A 40 °C - 1 s for power circuit || 110 A 40 °C - 10 min for power circuit || 260 A 40 °C - 1 min for power circuit
Protective Cover with
Per saperne di più arrow Weniger lesen arrow
*Gli articoli nuovi sono coperti da una garanzia Obso di 24 mesi.
I nostri articoli usati in precedenza e le opzioni di riparazione sono coperti da 12 mesi di garanzia Obso.


“Servizio super! Tutto è stato elaborato in modo molto rapido e competente e il supporto personale è stato eccellente. Sceglierei sempre di nuovo Obso Automation! Molte grazie per l'ottimo supporto”. - MJ
*La consegna e il ritiro il giorno stesso e successivo sono disponibili per le scorte delle nostre filiali nel Regno Unito e in Olanda. La consegna e il ritiro il giorno successivo e la consegna in 2 giorni sono disponibili per le scorte acquistate dai nostri partner. Nel 90% dei casi, se necessario, possiamo consegnare più velocemente del tempo previsto dal produttore.

Se necessario, sono disponibili anche opzioni standard per la consegna.


“Professionale, cortese e preciso. Pezzo obsoleto quotato il giorno stesso e fornito il giorno successivo” - PT
Siamo accreditati ISO 9001 per garantire la tranquillità del vostro acquisto.

Cosa dicono di noi i nostri clienti

Trustpilot

1

Step 1

    Parte aggiunta per richiesta

    2

    Passo 2

    Il vostro Account Manager personale è già al lavoro, fornendo risposte rapide e un servizio imbattibile.

    3

    Passo 3

    Non ci limitiamo a elaborare gli ordini, ma garantiamo una consegna senza intoppi, piena trasparenza e zero grattacapi.

    4

    Passo 4

    Più di 10.000 clienti si fidano di noi per un motivo. Richiedete subito il vostro preventivo e sperimentate l’automazione senza rischi, ritardi o incertezze.