LC2D25EHE
Schneider Electric
TeSys Deca reversing contactor - 3P - <= 440 V - 25 A AC-3 - 48...130 V AC/DC coil
Verfügbar
Jetzt Angebot einholen
- "LC2D25EHE is a 3-pole TeSys D reversing contactor from Schneider Electric for motor applications. Rated 25A AC-3 11kW@400V, it includes a 48-130V AC/DC low consumption electronic coil, 2NO+2NC aux contacts, a mechanical interlock. LC2D25EHE is a 3-pole TeSys D reversing contactor from Schneider Electric for motor applications up to 11kW@400V. It includes a 48-130V AC/DC low consumption electronic coil and 2NO+2NC built-in auxiliary contacts, NC mirror certified. Compact, DIN-rail mounting, with mechanical interlock and pre-wired reversing circuit, it procures reliability and durability. Available worldwide, it is multi-standards certified (IEC, UL, CSA, CCC, EAC, Marine) and Green Premium compliant (RoHs/Reach). Compact product, 90mm wide, for DIN-rail and panel mounting. Assembled with mechanical interlock and pre-wired reversing circuit. Clear separation between power and control circuits, easy front access to coil and auxiliary contacts connections. Equipped with an electronic coil, wide band voltage 48-130V, AC/DC compatible, low consumption. Provides 4 built-in auxiliary contacts 2NO + 2NC, NC contacts are mirror certified suitable to be included in the control of safety systems. High electrical durability, guaranteed for 2 million cycles at 25A AC-3 440V, for demanding motor switching applications. Robust design with high making and breaking capacities up to 20 In. Connection by screw clamp terminals."
| Specification | Value |
|---|---|
| Non-Overlap Time | 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact |
| Minimum Switching Current | 5 mA for signalling circuit |
| Control Circuit Voltage Limits | <= 0.1 Uc -40-70 °C drop-out AC/DC || 0.85...1.1 Uc -40-60 °C operational AC/DC || 1...1.1 Uc 60-70 °C operational AC/DC |
| Hold-In Power Consumption In W | 0.8-0.8 W 20 °C |
| Insulation Resistance | > 10 MOhm for signalling circuit |
| Inrush Power In Va | 25-25 VA 50/60 Hz 20 °C) |
| Coil Technology | built-in bidirectional peak limiting |
| Minimum Switching Voltage | 17 V for signalling circuit |
| Signalling Circuit Frequency | 25...400 Hz |
| Heat Dissipation | 0.8-0.8 W 50/60 Hz |
| Inrush Power In W | 24-24 W 20 °C |
| Auxiliary Contacts Type | mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1 |
| Hold-In Power Consumption In Va | 1.3-1.3 VA 20 °C) 50/60 Hz |
| Interlocking Type | mechanical |
| [Uc] Control Circuit Voltage | 48...130 V AC 50/60 Hz || 48...130 V DC |
| [Ue] Rated Operational Voltage | power circuit <= 690 V AC 25...400 Hz |
| Power Dissipation Per Pole | 3.2 W AC-1 || 1.25 W AC-3 || 1.25 W AC-3e |
| Average Impedance | 2 mOhm - Ith 40 A 50 Hz for power circuit |
| Auxiliary Contact Composition | 1 NO + 1 NC |
| [Ith] Conventional Free Air Thermal Current | 10 A (at 60 °C) for signalling circuit || 40 A (at 60 °C) for power circuit |
| Mounting Support | rail || plate |
| Control Circuit Type | AC 50/60 Hz AC/DC electronic || DC AC/DC electronic |
| Standards | EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || IEC 60335-1 |
| Safety Reliability Level | B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1 |
| Contactor Application | motor control || resistive load |
| Rated Breaking Capacity | 450 A at 440 V for power circuit conforming to IEC 60947 |
| Product Or Component Type | reversing contactor |
| Product Certifications | CCC || CSA || EAC || UL || KC || DNV-GL || LROS (Lloyds register of shipping) || UKCA |
| Irms Rated Making Capacity | 140 A AC for signalling circuit conforming to IEC 60947-5-1 || 250 A DC for signalling circuit conforming to IEC 60947-5-1 || 450 A at 440 V for power circuit conforming to IEC 60947 |
| Product Name | Tesys Deca green || TeSys Deca |
| Associated Fuse Rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1 || 63 A gG at <= 690 V coordination type 1 for power circuit || 40 A gG at <= 690 V coordination type 2 for power circuit |
| [Uimp] Rated Impulse Withstand Voltage | 6 kV IEC 60947 |
| Connections - Terminals | control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid || control circuit screw clamp terminals 2 1-4 mm²solid || power circuit screw clamp terminals 1 2.5-10 mm²flexible without cable end || power circuit screw clamp terminals 2 2.5-10 mm²flexible without cable end || power circuit screw clamp terminals 1 1-10 mm²flexible with cable end || power circuit screw clamp terminals 2 1.5-6 mm²flexible with cable end || power circuit screw clamp terminals 1 1.5-10 mm²solid || power circuit screw clamp terminals 2 2.5-10 mm²solid |
| Range | TeSys || TeSys Deca |
| Pole Contact Composition | 3 NO |
| Device Presentation | preassembled with reversing power busbar |
| Utilisation Category | AC-1 || AC-3 || AC-3e |
| [Ie] Rated Operational Current | 40 A (at <60 °C) at <= 440 V AC AC-1 for power circuit || 25 A (at <60 °C) at <= 440 V AC AC-3 for power circuit || 25 A (at <60 °C) at <= 440 V AC AC-3e for power circuit |
| Operating Time | 45...55 ms closing || 20...90 ms opening |
| Maximum Operating Rate | 3600 cyc/h 60 °C |
| Electrical Durability | 2 Mcycles 21 A AC-3 <= 440 V || 0.9 Mcycles 40 A AC-1 <= 440 V || 2 Mcycles 21 A AC-3e <= 440 V |
| Tightening Torque | control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 2.5 N.m screw clamp terminals flat Ø 6 mm || power circuit 2.5 N.m screw clamp terminals Philips No 2 || power circuit 1.7 N.m screw clamp terminals pozidriv No 2 || control circuit 2.5 N.m screw clamp terminals pozidriv No 2 |
| Poles Description | 3P |
| Overvoltage Category | III |
| Motor Power Kw | 5.5 kW at 220...230 V AC 50 Hz || 11 kW at 380...400 V AC 50 Hz || 11 kW at 415 V AC 50 Hz || 11 kW at 440 V AC 50 Hz || 15 kW at 500 V AC 50 Hz || 15 kW at 660...690 V AC 50 Hz |
| Maximum Horse Power Rating | 2 hp at 115 V AC 60 Hz for 1 phase motors || 3 hp at 230/240 V AC 60 Hz for 1 phase motors || 7.5 hp at 200/208 V AC 60 Hz for 3 phase motors || 7.5 hp at 230/240 V AC 60 Hz for 3 phase motors || 15 hp at 460/480 V AC 60 Hz for 3 phase motors || 20 hp at 575/600 V AC 60 Hz for 3 phase motors |
| [Ui] Rated Insulation Voltage | power circuit 690 V IEC 60947-4-1 || signalling circuit 690 V IEC 60947-1 |
| Mechanical Durability | 15 Mcycles |
| Device Short Name | LC2D |
| [Icw] Rated Short-Time Withstand Current | 50 A 40 °C - 10 min for power circuit || 120 A 40 °C - 1 min for power circuit || 240 A 40 °C - 10 s for power circuit || 380 A 40 °C - 1 s for power circuit || 100 A - 1 s for signalling circuit || 120 A - 500 ms for signalling circuit || 140 A - 100 ms for signalling circuit |
| Protective Cover | with |
Auf unsere gebrauchten Artikel und Reparaturoptionen gewähren wir 12 Monate Obso-Garantie.
„Super Service! Alles wurde sehr schnell und kompetent abgewickelt und die persönliche Betreuung war hervorragend. Ich würde mich jederzeit wieder für Obso Automation entscheiden! Vielen Dank für die tolle Unterstützung.“ - MJ
Bei Bedarf sind auch Standardoptionen für die Lieferung verfügbar.
„Professionell, zuvorkommend und genau. Veraltetes Teil am selben Tag angeboten und am nächsten Tag geliefert“ - PT
1
Step 1
Bauteil zur Anfrage hinzugefügt
2
Seite 2
Ihr persönlicher Kundenbetreuer ist bereits dabei und sorgt für schnelle Antworten und einen unschlagbaren Service.
3
Seite 3
Wir wickeln nicht nur Aufträge ab – wir garantieren eine reibungslose Lieferung, volle Transparenz und keine Kopfschmerzen.
4
Seite 4
Mehr als 10.000 Kunden vertrauen uns aus gutem Grund. Fordern Sie jetzt Ihr Angebot an und erleben Sie Automatisierung ohne Risiko, Verzögerungen oder Unsicherheit.
Google Reviews